Baldor mn792 Universal Remote User Manual


 
Parameter Table B-9MN792
Table B-1 Parameters Listed by Tag Number Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
528 RO Last Alarm ALARM STATUS Alarms 0x0000 : No Active Alarms
0x0001 : Over Speed
0x0002 : Missing Pulse
0x0004 : Field Over I
0x0008 : Heatsink Trip
0x0010 : Thermistor
0x0020 : Over Volts (VA)
0x0040 : SPD Feed back
0x0080 : Encoder Failed
0x0100 : Field Failed
0x0200 : 3 Phase Failed
0x0400 : Phase Lock
0x0800 : 5703 RCV Error
0x1000 : Stall Trip
0x2000 : Over I Trip
0xf005 : External Trip
0x8000 : Accts Failed
0xf001 : Autotune Error
0xf002 : Autotune Aborted
0xf200 : Config Enabled
0xf400 : No Keypad
0xf006 : Remote Trip
0xff05 : PCB Version
0xff06 : Product Code
No Active Alarms oo Output, 1
535 RW REM.SEQ.ENABLE SETUP PARAMETERS::AUX I/O Aux I/O 0 : False, 1 : True FALSE ov 2
536 RW REM.SEQUENCE SETUP PARAMETERS::AUX I/O Aux I/O 0x0000 to 0xFFFF 0x0000 ow 1
537 RO SEQ Status SETUP PARAMETERS::AUX I/O Aux I/O 0x0000 to 0xFFFF 0x0C03 ox Output
538 RO Current FBK.Amps DIAGNOSTICS Current Loop xxxx.x AMPS 0.0 Amps oy Output, 1, 3
539 RO Field I FBK.AMPS DIAGNOSTICS Current Loop xxxx.x AMPS 0.0 Amps oz Output, 1, 3
540 RW REM Trip Inhibit SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : Enabled 1 : Inhibited Enabled p0
541 RW REM Trip Delay SETUP PARAMETERS::CALIBRATION Alarms 0.1 to 600.0 Secs 10.0 Secs p1
542 RO Remote Trip ALARM STATUS Alarms 0 : False 1 : True FALSE p2 Output, 1
543 RW Zero CAL Inputs CONFIGURE DRIVE Up To Action Requested p3 1, 2, 3, 4
547 RW SPD.FBK.FILTER SETUP PARAMETERS::SPEED LOOP Menus 0.000 to 1.000 0.000 p7
549 RO Speed LOOP O/P DIAGNOSTICS Speed Loop -200 to 200 % 0.00% p9 Output, 2
594 RW CURR Decay Rate SETUP PARAMETERS::STOP RATES Stop Rates 0 to 200.00 0.00
605 RO ARM Volts FBK DIAGNOSTICS Unallocated 0 Volts Output
617 RW Field I Thresh SETUP PARAMETERS::FIELD CONTROL Field Control 0.00 to 100.00 % 80.00%
618 RO Up To Field SETUP PARAMETERS::FIELD CONTROL Field Control 0 : False 1 : True False Output
620 RW Invert SETUP PARAMETERS::RAMPS Ramps 0 : False 1 : True False