6-2 Programming MN792
Parameter Types
Each drive parameter is associated with a unique address, or tag. When connecting any parameter to drive
inputs, outputs, or links, this tag is designated as the source or destination address. These drive parameters are
listed by tag number, parameter name and menu group name in the appendix of this manual. There are only
two types of parameters: logic or value.
Logic
Logic parameters are boolean or either On (1) or Off (0). The keypad displays logic signals in a variety ways,
each associated with the On and Off state like Enabled/ Disabled, True/False, Positive/Negative, or Even/Odd.
Value
Value parameters have a range of values depending on its function. The display is formatted appropriately (for
example in percent). In all cases these values will not exceed five digits. For example, 100.00% is handled by
the controller as 10000 and 30.00 as 3000. Other value parameters can be HEX numbers, ordinals, and lists.
The ranges of these values depend on the parameter type.
Configuration Procedure
Before making any configuration changes with the keypad, you must set Configure Enable to Enabled. After
completing the changes, set Configure Enable to Disabled to accept the changes then select Parameter Save
to save to memory the changes you have made.
Note: Configuration changes are not allowed while running and will trip out on the alarm failure Configuration
Enabled if the drive is started while Configure Enable is Enabled.
Make configuration changes from the keypad as follows:
1. Set parameter System::Configure I/O::Configure Enable to Enabled.
2. Find the input or output you want to change.
3. Change the source and/or destination tag as required.
4. Set the or analog or digital I/O parameter calibrations as needed.
5. Set parameter Configure Enable to Disabled.
6. Save Parameters.