Baldor mn792 Universal Remote User Manual


 
6-10 Programming MN792
AUX I/O Continued
Example Bit Patterns
Sequence Status
Comment
0001 1011 0000 1011 Running
0000 0100 0100 1011 Tripped, Run High
0000 0100 0100 0111 Tripped, Run Low, Enable Low
0000 1100 0100 0111 Trip Acknowledged, Healthy o/p TRUE Alarm stays high until drive is restarted.
Example Serial commands using EIASCII REM. SEQUENCE
Tag 536, Mnemonic ow, Factory setting = 0x0C07
Remote
Trip
Alarm
Ack
Jog
Mode
Jog Start Enable Command
Start Drive 1 0 X 0 1 1 ow>0203
Stop Drive 1 0 X 0 0 1 ow>0201
Disable Drive 1 0 X X X 0 ow>0200
Jog Setpoint 1 1 0 0 1 0 1 ow>0205
Jog Setpoint 2 1 0 1 1 0 1 ow>020C
Remote Trip 0 0 X X X X ow>0000
Reset Alarm a) 1 1 0 0 0 0 ow>0300
Reset Alarm b) Healthy Output Bit 11
Reset Alarm c) 1 0 50 0 0 0 ow>0200
Drive Enable To Enable the drive in remote mode the following parameters must be
TRUE: REM.SEQ.ENABLE[535] and REM SEQUENCE [536] BIT 1.
Drive Start To Start the drive in remote mode the following parameters must be
TRUE: REM.SEQ.ENABLE[535] and REM SEQUENCE [536] BIT 0.
Drive Jog To Jog the drive in remote mode the following parameters must be
TRUE: REM.SEQ.ENABLE[535] and REM SEQUENCE [536] BIT 3.
Jog Mode To select the jog setpoint in remote mode the following parameters must be TRUE:REM.SEQ.ENABLE[535] and
REM SEQUENCE [536] BIT 4.
ACK Alarm To Acknowledge an alarm the following parameter must be TRUE:REM SEQUENCE [536] BIT 8.
Note: If remote sequencing is not enabled then REM SEQUENCE [536] BIT 8 is forced TRUE.
Remote Trip Alarm The Remote trip alarm is designed to signal a network fault to the drive. When using the Profibus interface,
all outputs are set to zero on link fail. If one of the outputs is REM SEQUENCE [536 ] the drive will trip after a
delay specified by REM TRIP DELAY (541). The Drive will then need a low > high transition on ACK Alarm
and Start before the drive may run again.
REM TRIP INHIBIT [540]
REM TRIP DELAY [541] REMOTE TRIP [542]
Disable remote trip. Delay before trip becomes active after bit
being cleared.
Status of the Remote trip alarm, OK, Warning (Remote
Seq Bit 9 FALSE and delay not expired), Active (Trip
active, timer expired and remote not inhibited).