Baldor mn792 Universal Remote User Manual


 
Parameter Table B-21MN792
Table B-3 Parameters Listed by Keypad Menu Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
59 RO UNFIL.ENCODER DIAGNOSTICS Calibration xxxxx RPM 0 RPM bn Output
64 RO UNFIL.SPD.ERROR DIAGNOSTICS Speed Loop xxx.xx % 0.00% bs Output
62 RO UNFIL.SPD.FBK DIAGNOSTICS Speed Loop xxx.xx % 0.03% bq Output
58 RO UNFIL.TACH INPUT DIAGNOSTICS Calibration xxx.xx % (h) 0.0% bm Output
37 RW FULL MENUS MENUS Menus 0 : Disabled 1 : Enabled Enabled b1
354 RW Parameter Save PARAMETER SAVE Unallocated Up To Action Requested ju 1
121 RW Change Password PASSWORD 0x0000 to 0xFFFF 0x0000 dd
120 RW Enter Password PASSWORD 0x0000 to 0xFFFF 0x0000 dc 1
155 RO Version Number SERIAL LINKS::SYSTEM PORT (P3) Unallocated 0x0000 to 0xFFFF eb Output
130 RW Mode SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP
System Port P3 0 : Disabled
1 : 5703 Master
2 : 5703 Slave
3 : CELite (EIASCII)
0 dm
198 RW P3 Baud Rate SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP
0:300 1:600 2:1200
3:2400 4:4800 5:9600
6:19200
9600 fi 2
187 RO Raw Input SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 xxx.xx % 0.00% f7 Output
189 RO Scaled Input SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 xxx.xx % 0.00% f9 Output, 2
132 RW SETPT. RATIO SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 -3.0000 to 3.0000 0.0000 do
133 RW SETPT. SIGN SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::5703 SUPPORT
5703 0 : Negative 1 : Positive Positive dp
332 RW Error Report SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0xFFFF 0x00C0 j8 1
329 RW GROUP ID (GID) SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0x0007 0x0000 j5
330 RW UNIT ID (UID) SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0x000F 0x0000 j6
506 RO TEC Option Fault SERIAL LINKS::TEC OPTION Tec Option 0 : None
1 : Parameter
2 : Type Mismatch
3 : Self Test
4 : Hardware
5 : Missing
None o2 Output
501 RW TEC Option IN 1 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0 nx
502 RW TEC Option IN 2 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0 ny
503 RW TEC Option IN 3 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0 nz
504 RW TEC Option IN 4 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0 o0
505 RW TEC Option IN 5 SERIAL LINKS::TEC OPTION Tec Option -32768 to 32767 0 o1
508 RO TEC Option OUT 1 SERIAL LINKS::TEC OPTION Tec Option xxxxx 0 o4 Output, 1
509 RO TEC Option OUT 2 SERIAL LINKS::TEC OPTION Tec Option xxxxx 0 o5 Output, 1
500 RW TEC Option Type SERIAL LINKS::TEC OPTION Tec Option 0 : None
1 : Rs485
2 : Profibus Dp
3 : Link
4 : Device Net
5 : Can Open
6 : Lonworks
7 : Type 7
None nw
507 RO TEC Option VER SERIAL LINKS::TEC OPTION Tec Option 0x0000 to 0xFFFF 0x0000 o3 Output, 1
128 RW ANOUT 1 SETUP PARAMETERS::AUX I/O Aux I/O -100.00 to 100.00 % 0.00% dk
129 RW ANOUT 2 SETUP PARAMETERS::AUX I/O Aux I/O -100.00 to 100.00 % 0.00% dl
94 RW AUX DIGOUT 1 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off cm
95 RW AUX DIGOUT 2 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off cn
96 RW AUX DIGOUT 3 SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On Off co
168 RW Aux Enable SETUP PARAMETERS::AUX I/O Aux I/O 0 : Off 1 : On On eo