Baldor mn792 Universal Remote User Manual


 
Section 9
Specifications & Product Data
Specifications & Product Data 9-1MN792
Identification
Baldor Control
Series 29 Digital DC
230/460VAC, 3 Phase
Input Voltage
BC29D7A
XXXX –CXX
Logic Power (Single Phase)
CO7 Internal Logic Transformer
CO1 Requires 115VAC Logic Power
CO2 Requires 230VAC Logic Power
Digital DC Control
Output Amps
Specifications:
Enclosure: Open Type (Chassis Mount)
Enclosure rating: Europe
North America / Canada
IP00 (Frame 1 is IP20)
UL Open type
Enclosure Heat Rise:
(if placed inside a totally enclosed cabinet)
The exposed metal surfaces dissipate approximately 50 Watts / m
2
for a
10 °C temperature rise above the ambient
Horsepower: 5–300 HP, 3 Phase
Voltage Range: 230 VAC Models
460 VAC Models
198-242 VAC 3φ 60 Hz / 50 Hz
414-550 VAC 3φ 60 Hz / 50 Hz
Input Frequency: 50/60 HZ ± 5%
Logic Power: Built in for size 1 and 2 controls.
External for Size 3, 4 and 5 controls.
115VAC, 1 phase with 3A fast blow fuse.
AC Line Contactor: Built in for size 1 and 2 controls.
External for Size 3, 4 and 5 controls.
3 Amps maximum at control rated voltage.
Output Voltage: DC; 0 – 1.2 times input VAC
Output Current: See Ratings
Output Current Limit: Adjustable 150% for 30 seconds, 200% for 10 seconds,
250% for 3 seconds
Service Factor: 1.0
Duty: Continuous
Ambient Operating Temperature: 0 to +45 °C (sizes 1 & 2); 0 to +40 °C (sizes 3, 4 and 5)
Derate Output 2% per °C over rating up to 55 °C Maximum
Rated Storage Temperature: – 25 °C to +55 °C
Humidity: 10 to 85% RH at 40 °C Non-Condensing
Altitude: Sea level to 1650 Feet (500 Meters)
Derate 1% per 660 Feet (200 Meters) above 1650 Feet
Maximum altitude 16,500 Feet (5,000 Meters)
Shock: 1G
Vibration: 0.5G at 10Hz to 60Hz
Climatic conditions: Class 3k3, as defined by EN60721–3–3 (1995)
Safety: Europe
North America / Canada
Overvoltage Category
Pollution Degree
EN50178 (1998), when installed inside suitable enclosure.
UL508C
Category III (3 phase power), Category II (1 phase Logic power)
Pollution Degree 2
EMC Compliance: All models
If external filters installed
European Directive 89 / 336 / EEC;
EN50082–1 (1992) and EN50082–2 (1995) for immunity
EN50081–2 (1994) Class A conducted emissions