Programming 6-31MN792
OP Station (Keypad) Local operation parameters are set using three menus.
1 SETUP PARAMETERS
2 OP-STATION
3 SETUP
Set Point
JOG Setpoint
Local Key Enable
1 SETUP PARAMETERS
2 OP-STATION
3 START UP VALUES
Setpoint
JOG Setpoint
Forward
Program
Local
1 SETUP PARAMETERS
2 OP-STATION
3 LOCAL RAMP
Ramp ACCEL Time
Ramp DECEL Time
Local Ramp
Accel Time
Decel Time
% S-Ramp
Up Key
Down Key
Reset Value
Local Setpoint
Stop Ramp
Note:
Local Setpoint (only active when the drive is in Local mode)
Parameter Descriptions
Local Key Enable
Enables the L/R on the keypad. This must be set true to allow the operator to select local and
remote modes.
Range: 0 : False
1 : True
Setpoint
Actual value of local setpoint.
Range: 0.00 to 100.00 %
Jog Setpoint
Actual value of local jog setpoint.
Range: 0.00 to 100.00 %
RAMP ACCEL TIME
Acceleration time used in Local mode.
Range: 0.1 to 600.0
Seconds
RAMP DECEL TIME
Deceleration time used in Local mode.
Range: 0.1 to 600.0
Seconds
FORWARD (Initial FWD Direction)
Startup mode of local direction on powerup. True = Forward.
Range: 0 : False
1 : True
LOCAL (Initial Local)
Startup mode of keypad L/R key on powerup. True = Local mode.
Range: 0 : False
1 : True
Program (Initial Program)
Startup mode of keypad PROG key on powerup. True = Program mode, to see the local setpoint.
Range: 0 : False
1 : True
Setpoint (Initial Setpoint)
Value of local setpoint on powerup.
Range: 0.00 to 100.00 %
JOG Setpoint (Initial Jog Setpoint)
Value of local jog setpoint on power up.
Range: 0.00 to 100.00 %
Password This keypad menu activates or deactivates the password protection feature.
1 PASSWORD
Enter Password
By-Pass Password
Change Password
Parameter Descriptions
Enter Password
Factory Setting = 0x0000 (No Password Is Set).
Range: 0x0000 to 0xFFFF
BYPASS PASSWORD Reserved parameter.
Factory Setting = FALSE
Range: 0 : False
1 : True
CHANGE PASSWORD
Factory Setting = 0x0000 (no change).
Range: 0x0000 to 0xFFFF