B-6 Parameter Table MN792
Table B-1 Parameters Listed by Tag Number Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
272 RW SPD.INT.TIME SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ADAPTION
Advanced 0.001 to 30.000 Secs 0.500 Secs hk
273 RW POS. LOOP P GAIN SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced -200.00 to 200.00 % 0.00% hl 4
274 RW I GAIN IN RAMP SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED
Advanced 0.0000 to 2.0000 1.0000 hm
284 RW ZERO SPD. LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 0.50% hw
285 RW ZERO IAD LEVEL SETUP PARAMETERS::SPEED LOOP::ADĆ
VANCED::ZERO SPD. QUENCH
Advanced 0.00 to 200.00 % 1.50% hx
286 RW RAMPING THRESH. SETUP PARAMETERS::RAMPS Ramps 0.00 to 100.00 % 0.50% hy
287 RW Auto Reset SETUP PARAMETERS::RAMPS Ramps 0 : Disabled 1 : Enabled Enabled hz
288 RW External Reset SETUP PARAMETERS::RAMPS Ramps 0 : Disabled 1 : Enabled Disabled i0
289 RW Setpoint 1 SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % 0.00% i1
290 RO Setpoint 2 (A3) SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop xxx.xx % 0.00% i2 Output
291 RW Setpoint 3 SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % 0.00% i3
292 RW SIGN 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 0 : Negative 1 : Positive Positive i4
293 RW RAMP O/P DEST SYSTEM::CONFIGURE I/O::BLOCK DIAGRAM Ramp Output 0 to 549 291 i5 2, 3
294 RW SPT SUM 1 DEST SYSTEM::CONFIGURE I/O::BLOCK DIAGRAM Setpoint Sum 1
Output
0 to 549 289 i6 2, 3
297 RO Speed Error DIAGNOSTICS Diagnostics xxx.xx % -0.01% i9 Output
298 RO Current Feedback DIAGNOSTICS Diagnostics xxx.xx % 0.00% ia Output
299 RO Current Demand DIAGNOSTICS Diagnostics xxx.xx % 0.00% ib Output
300 RO FIELD I FBK. DIAGNOSTICS Diagnostics xxx.xx % 0.00% ic Output
301 RW POS. I CLAMP SETUP PARAMETERS::CURRENT LOOP Current Loop -100.00 to 100.00 % 100.00% id
302 RW Contactor Delay SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 1.0 Secs ie
305 RW Trip Reset SETUP PARAMETERS::INHIBIT ALARMS Alarms 0 : False 1 : True TRUE ih
306 RW Source Tag SETUP PARAMETERS::STANDSTILL Standstill 0 to 549 89 ii 2, 3, 4
307 RW External Reset SETUP PARAMETERS::RAISE/LOWER Raise/Lower 0 : False 1 : True FALSE ij
308 RO Tach Input DIAGNOSTICS Diagnostics xxx.xx % (h) 0.0% ik Output
309 RW Input 0 SETUP PARAMETERS::SETPOINT SUM 1 Setpoint Sum 1 -200.00 to 200.00 % 0.00% il
329 RW GROUP ID (GID) SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0x0007 0x0000 j5
330 RW UNIT ID (UID) SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0x000F 0x0000 j6
332 RW Error Report SERIAL LINKS::SYSTEM PORT (P3)::P3 SETĆ
UP::BISYNCH SUPPORT
System Port P3 0x0000 to 0xFFFF 0x00C0 j8 1
337 RO Thermistor State ALARM STATUS Unallocated 0 : False 1 : True False jd Output
354 RW Parameter Save PARAMETER SAVE Unallocated Up To Action Requested ju 1
355 RW Ramp Rate SETUP PARAMETERS::JOG/SLACK Jog/Slack 0.1 to 600.0 Secs 1.0 Secs jv
357 RW Max Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop 0.00 to 105.00 % 105.00% jx
358 RW Min Demand SETUP PARAMETERS::SPEED LOOP::SETĆ
POINTS
Speed Loop -105.00 to 105.00 % -105.00% jy
359 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 1 (B5)
Digout 1 (B5) 0 : False 1 : True FALSE jz
360 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 : False 1 : True FALSE k0
361 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 : False 1 : True FALSE k1
362 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 0 : False 1 : True FALSE k2
363 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 0 : False 1 : True FALSE k3
364 RW Source Tag SYSTEM::CONFIGURE I/O::INTERNAL
LINKS::LINK 1
Link 1 0 to 549 0 k4 2, 3
365 RW Destination Tag SYSTEM::CONFIGURE I/O::INTERNAL
LINKS::LINK 1
Link 1 0 to 549 0 k5 2, 3