B-32 Parameter Table MN792
Table B-4 Parameters Listed by WB Block Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
360 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 : False 1 : True FALSE k0
44 RW Modulus SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 : False 1 : True TRUE b8
98 RW Source Tag SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) 0 to 549 122 cq 2, 3
196 RW Threshold (>) SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 2 (B6)
Digout 2 (B6) -300.00 to 300.00 % 0.00% fg 2
76 RO DIGOUT 3 (B7) DIAGNOSTICS Digout 3 (B7) 0 : Off 1 : On Off c4 Output
361 RW Inverted SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 : False 1 : True FALSE k1
45 RW Modulus SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 : False 1 : True TRUE b9
99 RW Source Tag SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) 0 to 549 125 cr 2, 3
197 RW Threshold (>) SYSTEM::CONFIGURE I/O::DIGITAL OUTĆ
PUTS::DIGOUT 3 (B7)
Digout 3 (B7) -300.00 to 300.00 % 0.00% fh 2
209 RW FLD.CTRL MODE CONFIGURE DRIVE Field Control 0 : Voltage Control
1 : Current Control
Voltage Control ft 2
210 RW FLD.VOLTS RATIO CONFIGURE DRIVE Field Control 0.00 to 100.00 % (h) 67.0% fu
183 RO Field Demand DIAGNOSTICS Field Control xxx.xx % 0.00% f3 Output
169 RO Field Enabled DIAGNOSTICS Field Control 0 : Disabled 1 : Enabled Disabled ep Output
184 RO FLD.FIRING ANGLE DIAGNOSTICS Field Control xxx.xx DEG 0.00 Deg f4 Output
170 RW Field Enable SETUP PARAMETERS::FIELD CONTROL Field Control 0 : Disabled 1 : Enabled Enabled eq 2
617 RW Field I Thresh SETUP PARAMETERS::FIELD CONTROL Field Control 0.00 to 100.00 % 80.00%
186 RW FLD. QUENCH
MODE
SETUP PARAMETERS::FIELD CONTROL Field Control 0 : Quench 1 : Standby Quench f6
185 RW FLD.QUENCH
DELAY
SETUP PARAMETERS::FIELD CONTROL Field Control 0.0 to 600.0 Secs 0.0 Secs f5
618 RO Up To Field SETUP PARAMETERS::FIELD CONTROL Field Control 0 : False 1 : True False Output
172 RW INT. GAIN SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS
Field Control 0.00 to 100.00 1.28 es
173 RW PROP. GAIN SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS
Field Control 0.00 to 100.00 0.10 et
171 RW Setpoint SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS
Field Control 0.00 to 100.00 % 100.00% er
192 RW BEMF FBK LAG SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 10 to 5000 100 fc
191 RW BEMF FBK LEAD SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 10 to 5000 100 fb
177 RW EMF GAIN SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 0.30 ex
176 RW EMF LAG SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 200.00 40.00 ew
175 RW EMF LEAD SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.10 to 50.00 2.00 ev
174 RW FLD. WEAK ENABLE SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0 : Disabled 1 : Enabled Disabled eu 2
178 RW MAX VOLTS SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 % 100.00% ey
179 RW MIN FLD.CURRENT SETUP PARAMETERS::FIELD CONĆ
TROL::FLD.CURRENT VARS::FLD.WEAK VARS
Field Control 0.00 to 100.00 % 10.00% ez 2
203 RO Inverse Time O/P DIAGNOSTICS Inverse Time xxx.xx % 200.0% fn Output, 2, 4
204 RW Aiming Point SETUP PARAMETERS::INVERSE TIME Inverse Time 0.00 to 103.00 % 103.00% fo 2, 4
199 RW Delay SETUP PARAMETERS::INVERSE TIME Inverse Time 0.1 to 600.0 Secs 10.0 Secs fj 2, 4
200 RW Rate SETUP PARAMETERS::INVERSE TIME Inverse Time 0.1 to 600.0 Secs 60.0 Secs fk 2, 4
212 RO Operating Mode DIAGNOSTICS Jog/Slack 0 : Stop
1 : Stop
2 : Jog Sp. 1
3 : Jog Sp. 2
4 : Run
5 : Take Up Sp. 1
6 : Take Up Sp. 2
7 : Crawl
Stop fw Output