DUMP ProcedureThis procedure will transfer the controls settings in a text format that is clear and easy to read.
1. Verify the Control is properly connected to the PC.
2. Use a standard communications software package installed at the PC. Set the COM port for 9600, 8,
1, None. Prepare the PC communications software to receive a standard ASCII text file (Capture
mode); use the file extension .UDP to differentiate it from .MMI format files.
3. Perform a PARAMETER SAVE of the Controls settings. This ensures the Dump matches the
Controls settings, (the listing is of the saved settings held in EEPROM).
4. Set the Serial Links::System Port (P3)::P3 Setup::Mode parameter to DISABLE.
5. Start downloading on the Control by selecting Serial Links::System Port (P3)::Dump MMI (TX) on the
keypad and pressing the UP (Y) key, when instructed.
6. The file ends in a Ctrlz. With some packages this automatically closes the file but if this is not the
case, when the Control says it has finished and the host has stopped scrolling text, close the file.
7. The ASCII file can now be stored like any other file on your disk drive.
The following partial file was produced by performing a MMI DUMP (TX) to a PC, as described above. The file
shows the Control default settings.
When printing this file, it is useful to select a Mono spaced font, such as Courier, so the text columns lineup.
Note that in the list shown, menus have been highlighted (bold) to make the list easier to use.
DIGITAL DC DRIVE
ISSUE:X.X
..MENU LEVEL
....DIAGNOSTICS
......SPEED DEMAND [89 ] = 0.00 %
......SPEED FEEDBACK [207 ] = 0.00 %
......SPEED ERROR [297 ] = 0.00 %
......CURRENT DEMAND [299 ] = 0.00 %
......CURRENT FEEDBACK [298 ] = 0.00 %
......POS. I CLAMP [87 ] = 0.0 %
......NEG. I CLAMP [88 ] = 0.0 %
......ACTUAL POS I LIM [67 ] = 0.0 %
......ACTUAL NEG I LIM [61 ] = 0.0 %
......INVERSE TIME O/P [203 ] = 200.00 %
......AT CURRENT LIMIT [42 ] = FALSE
......AT ZERO SPEED [77 ] = TRUE
......AT ZERO SETPOINT [78 ] = TRUE
......AT STANDSTILL [79 ] = TRUE
......STALL TRIP [112 ] = OK
......RAMPING [113 ] = FALSE
......PROGRAM STOP [80 ] = TRUE
......DRIVE START [82 ] = OFF
......DRIVE ENABLE [84 ] = DISABLED
......OPERATING MODE [212 ] = STOP
......FIELD ENABLE [169 ] = DISABLED
......FIELD DEMAND [183 ] = 0.00 %