Parameter Table B-19MN792
Parameter Values Continued R/W: RO = Read Only, RW = Read / Write
Table B-3 Parameters Listed by Keypad Menu
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
116 RO Health Store ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0000 d8 Output
115 RO Health Word ALARM STATUS Alarms 0x0000 to 0xFFFF 0x0200 d7 Output
528 RO Last Alarm ALARM STATUS Alarms 0x0000 : No Active Alarms
0x0001 : Over Speed
0x0002 : Missing Pulse
0x0004 : Field Over I
0x0008 : Heatsink Trip
0x0010 : Thermistor
0x0020 : Over Volts (VA)
0x0040 : SPD Feed back
0x0080 : Encoder Failed
0x0100 : Field Failed
0x0200 : 3 Phase Failed
0x0400 : Phase Lock
0x0800 : 5703 RCV Error
0x1000 : Stall Trip
0x2000 : Over I Trip
0xf005 : External Trip
0x8000 : Accts Failed
0xf001 : Autotune Error
0xf002 : Autotune Aborted
0xf200 : Config Enabled
0xf400 : No Keypad
0xf006 : Remote Trip
0xff05 : PCB Version
0xff06 : Product Code
No Active Alarms oo Output, 1
542 RO Remote Trip ALARM STATUS Alarms 0 : False 1 : True FALSE p2 Output, 1
472 RO SPEED FBK STATE ALARM STATUS Unallocated 0 : False 1 : True False n4 Output
112 RO Stall Trip ALARM STATUS Alarms 0 : OK 1 : Failed OK d4 Output
337 RO Thermistor State ALARM STATUS Unallocated 0 : False 1 : True False jd Output
523 RW Armature Current CONFIGURE DRIVE Calibration 2.0 to 15.0 AMPS 2.0 Amps oj 3
18 RO Autotune CONFIGURE DRIVE Current Loop 0 : Off 1 : On Off ai Output, 1
39 RW Configure Enable CONFIGURE DRIVE Unallocated 0 : Disabled 1 : Enabled Disabled b3 2
15 RW CUR.LIMIT/SCALER CONFIGURE DRIVE Current Loop 0.00 to 200.00 % 90.00% af
24 RW Encoder Lines CONFIGURE DRIVE Calibration 10 to 5000 1024 ao 2
22 RW Encoder RPM CONFIGURE DRIVE Calibration 0 to 6000 RPM 1750 RPM am
49 RW ENCODER SIGN CONFIGURE DRIVE Speed Loop 0 : Negative 1 : Positive Positive bd 2
524 RW Field Current CONFIGURE DRIVE Calibration 0.2 to 4.0 AMPS 0.2 Amps ok 3
209 RW FLD.CTRL MODE CONFIGURE DRIVE Field Control 0 : Voltage Control
1 : Current Control
Voltage Control ft 2
210 RW FLD.VOLTS RATIO CONFIGURE DRIVE Field Control 0.00 to 100.00 % (h) 67.0% fu
521 RW NOM Motor Volts CONFIGURE DRIVE Calibration 100 to 875 Volts 500 Volts oh 3
13 RW SPD.INT.TIME CONFIGURE DRIVE Speed Loop 0.001 to 30.000 Secs 0.500 Secs ad
14 RW SPD.PROP.GAIN CONFIGURE DRIVE Speed Loop 0.00 to 200.00 10 ae
47 RW SPEED FBK SELECT CONFIGURE DRIVE Speed Loop 0 : Arm Volts Fbk
1 : Analog Tach
2 : Encoder
3 : Encoder/Analog
Arm Volts Fbk bb
2
543 RW Zero CAL Inputs CONFIGURE DRIVE Up To Action Requested p3 1, 2, 3, 4
61 RO ACTUAL NEG I LIM DIAGNOSTICS Diagnostics xxx.xx % (h) -90.0% bp Output
67 RO ACTUAL POS I LIM DIAGNOSTICS Diagnostics xxx.xx % (h) 90.00% bv Output
50 RO ANIN 1 (A2) DIAGNOSTICS Analog Input 1 xxx.xx VOLTS 0.00V be Output
51 RO ANIN 2 (A3) DIAGNOSTICS Analog Input 2 xxx.xx VOLTS 0.00V bf Output
52 RO ANIN 3 (A4) DIAGNOSTICS Analog Input 3 xxx.xx VOLTS 0.00V bg Output
53 RO ANIN 4 (A5) DIAGNOSTICS Analog Input 4 xxx.xx VOLTS 0.00V bh Output
54 RO ANIN 5 (A6) DIAGNOSTICS Analog Input 5 xxx.xx VOLTS 10.00V bi Output
55 RO ANOUT 1 (A7) DIAGNOSTICS Analog Output 1 xxx.xx VOLTS (h) 0.00V bj Output
56 RO ANOUT 2 (A8) DIAGNOSTICS Analog Output 2 xxx.xx VOLTS (h) 0.00V bk Output
605 RO ARM Volts FBK DIAGNOSTICS Unallocated 0 Volts Output