Baldor mn792 Universal Remote User Manual


 
Parameter Table B-25MN792
Table B-3 Parameters Listed by Keypad Menu Continued
Tag R/W Name Keypad Menu WB Block Range Factory Setting MN Notes
306 RW Source Tag SETUP PARAMETERS::STANDSTILL Standstill 0 to 549 89 ii 2, 3, 4
11 RW Standstill Logic SETUP PARAMETERS::STANDSTILL Standstill 0 : Disabled 1 : Enabled Disabled ab
12 RW Zero Threshold SETUP PARAMETERS::STANDSTILL Standstill 0.00 to 100.00 % 2.00% ac
302 RW Contactor Delay SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 1.0 Secs ie
594 RW CURR Decay Rate SETUP PARAMETERS::STOP RATES Stop Rates 0 to 200.00 0.00
91 RW PROG STOP I LIM SETUP PARAMETERS::STOP RATES Stop Rates 0.00 to 200.00 % 100.00% cj
216 RW PROG STOP LIMIT SETUP PARAMETERS::STOP RATES Stop Rates 0.0 to 600.0 Secs 60.0 Secs g0
26 RW PROG Stop Time SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 0.1 Secs aq
217 RW Stop Limit SETUP PARAMETERS::STOP RATES Stop Rates 0.0 to 600.0 Secs 60.0 Secs g1
27 RW Stop Time SETUP PARAMETERS::STOP RATES Stop Rates 0.1 to 600.0 Secs 10.0 Secs ar
29 RW Stop Zero Speed SETUP PARAMETERS::STOP RATES Stop Rates 0.00 to 100.00 % 2.00% at
230 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -3.0000 to 3.0000 1.0000 ge
246 RW Destination Tag SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 0 to 549 100 gu 2, 3
231 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -300.00 to 300.00 % 100.00% gf
232 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 1 (A2)
Analog Input 1 -300.00 to 300.00 % -100.00% gg
233 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -3.0000 to 3.0000 1.0000 gh
234 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -300.00 to 300.00 % 100.00% gi
235 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 -300.00 to 300.00 % -100.00% gj
493 RO Output SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 2 (A3)
Analog Input 2 xxx.xx % 0.00% np Output, 2
236 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -3.0000 to 3.0000 1.0000 gk
249 RW Destination Tag SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 0 to 549 5 gx 2, 3
237 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -300.00 to 300.00 % 100.00% gl
238 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 3 (A4)
Analog Input 3 -300.00 to 300.00 % -100.00% gm
239 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -3.0000 to 3.0000 1.0000 gn
250 RW Destination Tag SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 0 to 549 48 gy 2, 3
240 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -300.00 to 300.00 % 100.00% go
241 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 4 (A5)
Analog Input 4 -300.00 to 300.00 % -100.00% gp
242 RW Calibration SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -3.0000 to 3.0000 1.0000 gq
247 RW Destination Tag SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 0 to 549 301 gv 2, 3
243 RW Max Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -300.00 to 300.00 % 200.00% gr
244 RW Min Value SYSTEM::CONFIGURE I/O::ANALOG INĆ
PUTS::ANIN 5 (A6)
Analog Input 5 -300.00 to 300.00 % -200.00% gs
245 RW % TO GET 10V SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 -300.00 to 300.00 % 100.00% gt
362 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 0 : False 1 : True FALSE k2
464 RW Offset SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 -100.00 to 100.00 % 0.00% mw
251 RW Source Tag SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 1 (A7)
Analog Output 1 0 to 549 62 gz 2, 3
248 RW % TO GET 10V SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 -300.00 to 300.00 % 100.00% gw
363 RW Modulus SYSTEM::CONFIGURE I/O::ANALOG OUTĆ
PUTS::ANOUT 2 (A8)
Analog Output 2 0 : False 1 : True FALSE k3