Mitsubishi Electronics FX3G Universal Remote User Manual


 
8 Installation In Enclosure
8.4 Procedures for Installing on and Detaching from DIN Rail
108
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
8.4.3 Installation of input/output powered extension unit/block and special function block
1 Push out the DIN rail mounting hook (A in the right fig-
ure) of the input/output extension block.
For input/output powered extension units, 8-point type input/output
extension blocks (except for the FX
2N-8EYR-S-ES/UL) and special
extension units/blocks, this operation is unnecessary.
2 Fit the upper edge of the DIN rail mounting groove (B
in the right figure) onto the DIN rail.
3 Push the product against the DIN rail.
Keep a gap of 1 to 2 mm (0.04" to 0.08") between the products.
4 Connect the extension cable.
For the procedures on connecting the extension cable, refer to Subsection 8.6.5.
Rear panel Rear panel
A
1
B
3