Mitsubishi Electronics FX3G Universal Remote User Manual


 
5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
60
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
5.2.4 Cautions on connecting peripheral equipment by way of expansion board or special
adapter
When connecting peripheral equipment (programming tool or GOT [CPU direct connection]) by way of the
FX
3G-232-BD, FX3G-422-BD or FX3U-232ADP(-MB), set the connection channel (CH1 or CH2) as follows. If
the connection channel is not specified with the status below, communication error may occur in the
connected peripheral equipment.
For details, refer to the Data Communication Edition.
- Set to "K0" the special data register for communication format setting of the channel connecting the
peripheral equipment (CH1: D8400 or D8120, CH2: D8420).
- Set the communication parameter "PLC system [2]" of the channel connecting the peripheral equipment
to "Not set" (as shown in the window below).
5.2.5 Cautions on write during RUN
In FX3G PLCs, write during RUN (program changes in the RUN mode) is enabled using the following
programming tools.
For the operating procedure of and cautions on write during RUN,
refer to the manual of the used programming tool.
Programming tools supporting write during RUN
English version
Programming tool Version Remarks
GX Works2
*1
(SW DNC-GXW2-E)
Ver. 1.08J or later
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.40.
Ver. 1.62Q or later
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.40.
GX Developer
*2
(SW D5C-GPPW-E)
Ver. 2.00A or later
Writing in the instruction and device ranges during RUN is supported in FX2N PLCs
Ver. 1.00.
Ver. 5.00A or later
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
Ver. 8.72A or later
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.10.
Ver. 8.78G or later
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.10.
FX-PCS/WIN-E
*2
Ver. 3.00 or later
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
Leave this unchecked.