5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
59
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
5.2.2 In the case of programming tool (version) not applicable
Inapplicable programming tools can be used by selecting an alternative PLC model.
1. Alternative model setting
*1. "FX2N" is selected when the FX-10P(-E) is used.
2. Contents of restrictions
Programming is enabled only for the range of functionality available in the PLC selected as the alternative
model, such as instructions, device ranges and program sizes. When the FX-10P(-E) is used, the range of
functionality is limited to that available in the FX
2N PLC.
Use a programming tool that can select either FX
3G to change parameters, i.e. memory capacity, file
register capacity, etc.
The built-in USB port cannot be used for programming communication.
5.2.3 Program transfer speed and programming tools
1. Built-in USB communication
The FX3G PLC has a built-in USB communication port, and performs program writing, program reading and
monitoring at high speed (12 Mbps) with a personal computer that supports USB.
1) Supported programming tools
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later)
2) In programming tools not supporting USB
Communication is performed via RS-422 or RS-232C.
2. RS-422/RS-232C communication
The FX3G PLC can write and read programs and perform monitoring at 115.2 kbps through RS-422/RS-232C
communication.
1) 115.2 kbps supported programming tools
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later), FX-30P (Ver. 1.00 or later)
2) 115.2 kbps supported interfaces
- Standard built-in port (RS-422) or expansion board FX
3G-422-BD for RS-422
When the RS-232C/RS-422 converter FX-232AWC-H is connected.
- Expansion board FX
3G-232-BD for RS-232C
- Special adapter FX
3U-232ADP(-MB) for RS-232C
3) In programming tools not supporting 115.2 kbps
Communication is executed at 9,600 or 19,200 bps.
Model to be programmed Model to be set Priority High Low
FX3G PLC FX3G
FX1N
*1
FX2N
*1
FX2