Mitsubishi Electronics FX3G Universal Remote User Manual


 
9 Preparation for Wiring and Power Supply Wiring Procedures
9.2 Cable Connecting Procedures
125
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
3. Wire end treatment
The solderless terminal size depends on the terminal screw size and wiring method.
- Use solderless terminals of the following size.
- Tighten the terminals to a torque of 0.5 to 0.8 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may
cause equipment failures or malfunctions.
In the case of M3 terminal screw
When one wire is connected to one terminal
<Reference>
When two wires are connected to one terminal
<Reference>
Terminal Manufacturer Type No. Certification Pressure Bonding Tool
JAPAN SOLDERLESS TERMINAL MFG CO LTD (JST)
FV1.25-B3A
UL Listed YA-1(JST)
FV2-MS3
Terminal Manufacturer Type No. Certification Pressure Bonding Tool
JAPAN SOLDERLESS TERMINAL MFG CO LTD (JST) FV1.25-B3A UL Listed YA-1(JST)
TerminalTerminal
Terminal
screw
Crimp
terminal
6.2mm(0.24")
or less
3.2(0.13")
6.2mm(0.24")
or less
3.2(0.13")
Terminal
screw
Crimp
terminal
Terminal
6.2mm(0.24")
or less
3.2(0.13")
6.3mm(0.25")
or more
6.2mm(0.24")
or less
3.2(0.13")
6.3mm(0.25")
or more