Mitsubishi Electronics FX3G Universal Remote User Manual


 
16 Input/Output Extension Blocks
276
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
16.11 FX2N-8EYT, FX2N-16EYT, FX2N-16EYT-C (Transistor Output)
16.11.1 Product specifications
The generic specifications are identical to the main unit specifications.
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapters.
Refer to Chapter 12 for output wiring.
1. Power supply specifications
2. Weight and Other specifications (External dimensions are described later.)
3. Output specifications (Transistor output type)
Item FX2N-8EYT FX2N-16EYT FX2N-16EYT-C
Product type FX2N extension block FX2N connector type extension block
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Item FX2N-8EYT FX2N-16EYT FX2N-16EYT-C
MASS (Weight) 0.2kg (0.44lbs) 0.3kg (0.66lbs)
Other
The extension cable is already connected to the extension block.
Accessories: Label for indication of input/output number
The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Item FX2N-8EYT FX2N-16EYT FX2N-16EYT-C
Output Points 8 points 16 points
Connection type Vertical terminal block (M3 screws) Connector terminal block
Output unit/type Transistor/sink output
External power supply 5 to 30V DC
Output circuit insulation Photo-coupler insulation
Indication of output operation Activation of the photo-coupler will light the LED indicator lamp on panel.
Max. load
Resistance load
0.5A/point
The total load current per common should be
as follows:
4 output points/common: 0.8A or less
8 output points/common: 1.6A or less
0.3A/point
The total load current per common should be
as follows:
16 output points/common: 1.6A or less
Inductive load
12W/24V DC
The total of inductive loads per common
terminal should be the following value.
4 output point/common terminal: 19.2W or
less/24V DC
8 output points/common terminal: 38.4W or
less/24V DC
7.2 W/24V DC
The total of inductive loads per common
terminal should be the following value.
16 output points/common terminal: 38.4W
or less/24V DC
Open circuit leakage current 0.1mA/30V DC
Min. load -
Response time
OFF ON 0.2ms or less for 200mA (at 24V DC)
ON OFF 0.2ms or less for 200mA (at 24V DC)
Output circuit configuration
Load
Fuse
DC power
supply unit
Fuse
DC power
supply unit
Y
COM1
Y
COM2
Load
Fuse
DC power
supply unit
Y
COM
Fuse
DC power
supply unit
Y
COM