Mitsubishi Electronics FX3G Universal Remote User Manual


 
9 Preparation for Wiring and Power Supply Wiring Procedures
9.2 Cable Connecting Procedures
128
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
9.2.3 Terminal block for Europe [expansion board and special adapters]
The expansion board and special adapters of a terminal block type have terminal blocks for Europe.
1. Applicable products
2. Compliant electric wires and tightening torque
*1. Old model name : CRIMPFOX ZA 3
*2. Old model name : CRIMPFOX UD 6
3. Treatment of electric wire ends
Treat the ends of stranded wires and solid wires without coating or using bar terminals with insulating sleeve.
Tighten the terminals to a torque of 0.22 to 0.25 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may cause
equipment failures or malfunctions.
Treatment of stranded wires and solid wires without coating
- Twist the ends of stranded wires tightly so that loose wires will not
stick out.
- Do not solder-plate the electric wire ends.
Treatment using bar terminal with insulating sleeve
It may be difficult to insert the electric wire into the insulating sleeve
depending on the thickness of the electric wire sheath. Select the
electric wire referring to the outline drawing.
<Reference>
*3. Old model name : CRIMPFOX ZA 3
*4. Old model name : CRIMPFOX UD 6
4. Tool
For tightening the terminal, use a commercially available small screwdriver having a straight form that is
not widened toward the end as shown right.
Note :
If the diameter of screwdriver grip is too small, tightening torque will not be
able to be achieved. To achieve the appropriate tightening torque shown in
the table above, use the following screwdriver or appropriate replacement
(grip diameter : approximately 25 mm(0.98")).
<Reference>
Classification Model names
Expansion Board FX3G-4EX-BD, FX3G-2EYT-BD, FX3G-485-BD, FX3G-2AD-BD, FX3G-1DA-BD
Special Adapters
FX3U-485ADP(-MB), FX3U-4AD-ADP, FX3U-4DA-ADP, FX3U-3A-ADP, FX3U-4AD-PT-ADP,
FX3U-4AD-PTW-ADP, FX3U-4AD-PNK-ADP, FX3U-4AD-TC-ADP
Electric wire size
(stranded wire/solid wire)
Tightening
torque
End treatment
One electric wire
0.3 to 0.5 mm
2
(AWG22 to 20)
0.22 to 0.25 N•m
Remove the coating of the stranded wire, twist the core wires,
and connect the wires directly.
Remove the coating from the solid wire, and connect the wire
directly.
Two electric wires
0.3 mm
2
(AWG22) ×2
Bar terminal with
insulating sleeve
0.3 to 0.5 mm
2
(AWG22 to 20)
(Refer to the following outline
drawing of bar terminal.)
Bar terminal with insulating sleeve
(recommended product)
AI 0.5-8WH : Phoenix Contact
Caulking tool
CRIMPFOX 6
*1
: Phoenix Contact
(CRIMPFOX 6T-F
*2
: Phoenix Contact)
Manufacturer Model names Caulking tool
Phoenix Contact AI 0.5-8WH
CRIMPFOX 6
*3
( or CRIMPFOX 6T-F
*4
)
Manufacturer Model names
Phoenix Contact SZS 0.4 x 2.5
9mm
(0.36")
Stranded wire/solid wire
8mm
(0.32")
Contact area
(Crimp area)
14mm(0.56")
2.6mm
(0.11")
Insulating sleeve
Bar terminal with insulating sleeve
0.4mm
(0.02")
2.5mm
(0.1")
With
straight tip