Mitsubishi Electronics FX3G Universal Remote User Manual


 
16 Input/Output Extension Blocks
266
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
16.8 FX2N-8EYR-ES/UL, FX2N-8EYR-S-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
16.8 FX2N-8EYR-ES/UL, FX2N-8EYR-S-ES/UL, FX2N-16EYR-ES/UL
(Relay Output)
16.8.1 Product specifications
The generic specifications are identical to the main unit specifications.
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapters.
Refer to Chapter 12 for output wiring.
1. Power supply specifications
2. Weight and Other specifications (External dimensions are described later.)
3. Output specifications (Relay output type)
Item FX2N-8EYR-ES/UL FX2N-16EYR-ES/UL FX2N-8EYR-S-ES/UL
Product type FX2N extension block
Rated voltage 24V DC (supplied from main unit and input/output powered extension unit)
Item FX2N-8EYR-ES/UL FX2N-16EYR-ES/UL FX2N-8EYR-S-ES/UL
MASS (Weight) 0.2kg (0.44lbs) 0.3kg (0.66lbs)
Other
The extension cable is already connected to the extension block.
Accessories: Label for indication of input/output number
The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Item FX2N-8EYR-ES/UL FX2N-16EYR-ES/UL FX2N-8EYR-S-ES/UL
Output Points 8 points 16 points
8 points
(All points have separate reference
terminals (commons))
Connection type Vertical terminal block (M3 screws)
Output type Relay
External power supply
30V DC or less
240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
Output circuit insulation Mechanical insulation
Indication of output operation Supplying power to the relay coil will light the LED indicator lamp on panel.
Max. load
Resistance load
2A/point
The total resistance load current per common should
be as follows:
4 output points/common: 8A or less
8 output points/common: 8A or less
2A/point
Inductive load
80VA
For the product life, refer to Subsection 14.4.3.
For cautions on external wiring, refer to Subsection 12.1.3.
Open circuit leakage current -
Min. load 5V DC, 2mA (reference values)
Response time
OFF ON Approx. 10ms
ON OFF Approx. 10ms
Output circuit configuration
A
common number applies to the of [COM ].
Load
DC power
supply unit
Fuse
Y
AC power
supply unit
Fuse
Y
COM
COM
Load
DC power
supply unit
Fuse
Y0
AC power
supply unit
Fuse
Y0
Y7
Y7