Avaya S8100 Home Theater Server User Manual


 
1Install and cable a G600 cabinet
Check customer’s order
S8100 Installation and Upgrades 59
November 2003
The other Environmental Considerations and System Protection requirements described in the Hardware
Guide for Avaya Communication Manager under “Site Requirements” apply to the G600 as well.
Check customer’s order
1 Check the customer’s order and the shipping packing lists to confirm that all equipment is
included.
2 Report missing equipment to an Avaya representative.
3 Check the system’s adjuncts, and report any damage according to local shipping instructions.
Correct shipping errors
1 Red-tag any defective or over-shipped equipment, and return it according to instuctions from
National Parts.
2 Direct any short-shipped reports to National Parts. Contact the appropriate location for specific
instructions. For a streamlined implementation, call 1-800-772-5409.
Table 1: Power sources and receptacles for AC-powered cabinets
Cabinet’s style and power-
distribution unit Power sources Power input receptacles
Rack-mounted cabinet – AC power
supply
(650A integrated power supply)
No integrated DC power supply – DC
rectifiers can be used if desired; follow
manufacturer’s instructions.
Single-phase 120-VAC
source, with neutral
Single-phase 240-VAC
source, with neutral
120-VAC, 60-Hz NEMA 5-15R
receptacle
240-VAC, 50-Hz IEC 320
receptacle
Installations in Japan use
country-specific 100-/200-VAC,
50-/60-Hz receptacles
Table 2: Circuit breakers for AC-powered cabinets
Cabinet’s type Circuit breaker’s size
Rack-mounted cabinet (120 VAC, 60 Hz) 15 A
Rack-mounted cabinet (240 VAC, 50 Hz) 10 A