1 Install and cable a G600 cabinet
Check AC power and ground for G600
76 S8100 Installation and Upgrades
November 2003
Figure 10: Single-cabinet G600 grounding
Figure notes
1 10 AWG (#25) (6 mm
2
) wire to
coupled bonding conductor (CBC).
2 6 AWG (#40) (16 mm
2
) ground wire from
single-point ground block to the approved
building ground.
1
2
cadpgnd1 LJK 102500