Mitsubishi Electronics IB-1500193(ENG)-D Home Theater Server User Manual


 
3 - 32
3 Setup
MITSUBISHI CNC
MDS-D-SVJ3 Series: Regenerative resistor type
Set the regenerative resistor type.
bit F-8 : amp(bit F-C) / rtyp(bit B-8)
Resistor built-in drive unit : 10
Setting prohibited : 11
MR-RB032 : 12
MR-RB12 or GZG200W39OHMK : 13
MR-RB32 or GZG200W120OHMK 3 units connected in parallel : 14
MR-RB30 or GZG200W39OHMK 3 units connected in parallel : 15
MR-RB50 or GZG300W39OHMK 3 units connected in parallel : 16
MR-RB31 or GZG200W20OHMK 3 units connected in parallel : 17
MR-RB51 or GZG300W20OHMK 3 units connected in parallel : 18
Setting prohibited : 19-1F
Setting prohibited : 20-23
FCUA-RB22 : 24
FCUA-RB37 : 25
FCUA-RB55 : 26
Setting prohibited : 27
R-UNIT1 : 28
R-UNIT2 : 29
R-UNIT3 : 2A
R-UNIT4 : 2B
R-UNIT5 : 2C
FCUA-RB75/2 2 units connected in parallel : 2D
FCUA-RB55 2 units connected in parallel : 2E
Setting prohibited : 2F
bit 7-4 : emgx External emergency stop function
Set the external emergency stop function. (Do not set a value other than specified.)
0: Disable 4: Enable
bit 3-0 :
Not used. Set to "0".
#2237 SV037 JL Load inertia scale
Set the motor axis conversion total load inertia including motor itself in proportion to the motor
inertia.
SV037(JL)=(Jm+Jl)/Jm×100
Jm: Motor inertia
Jl: Motor axis conversion load inertia
For linear motor, set the gross mass of the moving sections in kg unit.
<<Drive monitor load inertia ratio display>>
Set SV035/bitF=1 and imbalance torque and friction torque to both SV032 and SV045, and then
repeat acceleration/deceleration for several times.
---Setting range---
For general motor: 0 to 5000 (%)
For linear motor 0 to 5000 (kg)
emgx
rtyp
amp
0000