4 Servo Adjustment
MITSUBISHI CNC
#2248 SV048 EMGrt Vertical axis drop prevention time
Input the time required to prevent the vertical axis from dropping by delaying READY OFF until the
brake works at an emergency stop.
Increase in increments of 100ms at a time, find and set the value where the axis does not drop.
When using a motor with a break, set to "200ms" as a standard.
When the pull up function is enabled (SV033/bitE=1), the pull up is established during the drop
prevention time.
---Setting range---
0 to 20000 (ms)
#2255 SV055 EMGx Max. gate off delay time after emergency stop
Set the time required between an emergency stop and forced READY OFF.
Set the maximum value "+ 100ms" of the SV056 setting value of the servo drive unit electrified by the
same power supply unit.
When executing the vertical axis drop prevention, the gate off will be delayed for the length of time
set at SV048 even when SV055's is smaller than that of SV048.
---Setting range---
0 to 20000 (ms)
#2256 SV056 EMGt Deceleration time constant at emergency stop
Set the time constant used for the deceleration control at emergency stop.
Set the time required to stop from rapid traverse rate (rapid).
The standard setting value is EMGt<=G0tL*0.9.
However, note that the standard setting value differs from the above-mentioned value when the
setting value of "#2003:smgst Acceleration and deceleration modes bit 3-0:Rapid traverse
acceleration/deceleration type" is 8 or F. Refer to Instruction Manual of the drive unit (section
"Deceleration control") for details.
When the axis is used in the synchronous control, set the same value with minus sign to both axis.
If one of the axis switches to dynamic brake by an alarm during deceleration control, another axis will
also switch.
---Setting range---
-20000 to 20000 (ms)
1. Always set deceleration control when using the vertical axis drop prevention control setting.
2. In the system with MDS-D-SVJ3 unit only, configure so that the contactor is controlled directly by
the axis which controls the vertical axis drop prevention control.
3. If an alarm, for which dynamic brake stopping is designated, occurs with the axis for which vertical
axis drop prevention control is active, the function will not activate. To prevent axis dropping under
all conditions, provide measures on the machine side by installing a balance unit, etc.
4. In consideration of the relay delay time for the break control, set the vertical axis drop prevention
time.
CAUTION