98
Reference value write
request
• Use this area to save the measured
reference value in the flash ROM of the
QD73A1.
• When this area setting is changed to 1, the
measured reference value is saved in the
flash ROM.
• When " Reference value
measurement flag" is set to 1, the value is
written to the flash ROM. If
" Reference value measurement flag"
is set to the value other than 1, the error
"Reference value write error" (error code:
132) occurs and the value is not written.
• The QD73A1 set this area to 0 when the
value saving in the flash ROM is completed.
This process is the same when an error
occurs and the value is not written.
For details on the accumulated pulse error
detection function, refer to the following.
Page 223, Section 11.9
0: No request
1: Requested
0: No
request
411
Item Description Setting range
Default
value
Buffer
memory
address
(decimal)
Cd.20
Md.20
Md.20