CHAPTER 6 VARIOUS SETTINGS
6
6.2 Switch Setting
6.2.2 Accumulated pulse setting
(b) Accumulated pulse amount and analog output voltage from the QD73A1
The analog output voltage from the QD73A1 is controlled in proportion to accumulated pulse amount.
The following is an example of selecting an option in "Accumulated pulse setting".
Ex.
Maximum speed: 4Mpulse/s, position loop gain: 30s
-1
If the number of accumulated pulses is 133333, "-148000 to 148000 pulse" should be selected in
"Accumulated pulse setting" so that analog output voltage will not be saturated.
Selection 5
37000* 74000* 111000* 148000*
Selection 6 Selection 7 Selection 8
Analog
output voltage
Accumulated
pulse
If the accumulated pulse exceeds the amount marked *,
an excessive error occurs.
If the accumulated pulse exceeds the amount marked *,
an excessive error occurs.
Selection 1
3700*3480 6960 7400* 10440 11100* 13920 14800*
Selection 2 Selection 3 Selection 4
Analog
output voltage
Gain
adjustment
value
Gain
adjustment
value
Gain
adjustment
value
Gain
adjustment
value
-3480-6960
Accumulated
pulse
34800 69600 104400 139200
-69600 -34800
Accumulated
pulse
==
Maximum speed
Position loop gain
=
4000000
30
133333 pulses