CHAPTER 9 MAJOR POSITIONING CONTROL
9
9.7 Operation Timing and Processing Time of Major Positioning Control
9.7 Operation Timing and Processing Time of Major
Positioning Control
This section explains the operation timing and processing time of major positioning control.
*1 This is an indication of internal commands, and does not match with the actual analog output waveform.
The following values apply to t1 to t3.
t1 t2 t3
0.7 to 1.2ms 0 to 0.5ms 0 to 0.5ms
Positioning start signal
(Y21 to Y23)
BUSY signal
(X14)
Positioning complete signal
(X15)
t1
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
t2
t3
Positioning start complete signal
(X21 to X23)
OPR complete signal
(X13)
Major positioning control
*1
v