4 - 6
MELSEC-
A
4 INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
(2) Other precautions
(a) Main body
The main body case is made of plastic. Take care not to drop or apply
strong impacts onto the case.
(b) Installation environment
Do not install the module in the following type of environment.
Where the ambient temperature exceeds the 0 to 55
°
C range.
Where the ambient humidity exceeds the 10 to 90%RH range.
Where there is sudden temperature changes, or where dew condenses.
Where there is corrosive gas or flammable gas.
Where there are high levels of dust, conductive powder, such as iron
chips, oil mist, salt or organic solvents.
Where the module will be subject to direct sunlight.
Where there are strong electric fields or magnetic fields.
Where vibration or impact could be directly applied onto the main body.