14 - 12
MELSEC-
A
14 TROUBLESHOOTING
Division of
error
Error
code
Error name Description Action at occurrence of error
206
Count method
movement
amount fault
The “Setting for the movement amount after
near-point dog ON” zero point return detail
parameter is smaller than the distance
necessary for deceleration and stop from the
zero point return speed in count method 1), 2)
machine zero point return.
Machine zero point return start is not carried
out.
207
Zero point return
request ON
The zero point return request flag is set at the
start of high-speed zero point return
(positioning start No. 9002).
High-speed zero point return start is not carried
out.
208
Outside creep
speed range
The value specified as a creep speed exceeds
the value specified as a zero point return
speed.
Machine zero point return start is not carried
out.
209
Zero point return
restart not
possible
The restart command is turned ON after the
machine zero point return is stopped using a
stop signal.
The restart is not carried out.
213
ABS transfer
time-out
Normal communication with the servo amplifier
could not be made during absolute position
restoration.
Do not perform absolute position restoration.
214
ABS transfer
check sum
JOG 300
Outside JOG
speed range
The JOG speed is out of the setting range at
the start of JOG operation.
If the setting is out of the range at the start of
JOG operation, JOG operation is not carried
out.