14 TROUBLESHOOTING
Relevant buffer memory address
remote input/output device, or
remote register
Setting range Remedy
Axis 1 Axis 2
0 150 0, 1, 2, 3
Change the setting to within the setting range and turn
OFF then ON the remote station READY signal
[RX(n+7)B].
1 151 1 to 65535
2 152 1 to 65535
3 153 1, 10, 100, 1000
4 154 0, 1, 2, 3
5 155 0, 1
6
7
156
157
(In standard mode)
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
(In stepping motor mode)
1 to 62500 [pulse/s]
1 to 37500000 [mm/min, etc.]
8
9
158
159
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
10
11
160
161
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
12
13
162
163
(In standard mode)
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
(In stepping motor mode)
1 to 62500 [pulse/s]
1 to 37500000 [mm/min, etc.]
16
17
166
167
(In standard mode)
[mm] [inch] [pulse]
-2147483648 to 2147483647
[degree] 0 to 35999999
(In stepping motor mode)
[mm] [inch] [pulse]
–134217728 to 134217727
[degree] 0 to 35
Change the setting to within the setting range.
In case of a unit other than “degree,” change the settings
so that the lower limit value is smaller than the upper limit
value.