4 - 15
MELSEC-
A
4 INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
4.4.2 Transmission speed setting of module
Set the transmission speed of the D75P2.
*The default value (factory setting) is "0".
[1] Setting bases
1) The number that can be set is within the range "0" to "4".
2) The number is as indicated in the following table.
Communication speed to be set Setting number
156[kbps] 0
625[kbps] 1
2.5[Mbps] 2
5[Mbps] 3
10[Mbps] 4
* Setting numbers "5" to "9" cannot be used. If any of numbers "5" to "9" is set, the "L
ERR" lamp of the "CC-Link status indicator LEDs" will turn on at the time of data
communication.
[2] Setting method
Insert a flat-blade screwdriver into the arrow-shaped groove, and turn it to the numeral
of the number to be set.
Turn the arrow to the numeral of the number to be set.
Example) When the communication speed is 5 [Mbps], set the arrow to value "3".