DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-554DS1-BD (DS1 Interface Circuit Pack)
3
are detected for 30 minutes. The value in the Aux Data field indicates the
type of hardware problem. However, when this error is reported with Aux
Data in the range of 4352 to 4358, it indicates the circuit pack has
reported a hardware failure. Escalate this problem.
g. The DS1 Interface circuit pack has detected a transient hardware logic
error (for example, program logic inconsistency). This error will disappear
when no faults are detected for 100 minutes. The value in Aux Data field
indicates the type of hardware problem.
h. CSU Module or T1 Sync Splitter missing. The
Near-End CSU Type
field
on the
add ds1
form has been administered as
integrated
but the
120A1 CSU Module or T1 Sync Splitter is not physically connected (or is
improperly connected) to the TN767E board on the back of the port
carrier.
If using the 120A1 CSU Module or T1 Sync Splitter, plug (or replug) the
CSU Module/T1 Sync Splitter into the TN767E circuit pack’s connector on
the I/O connector panel on back of the carrier. Otherwise, change the
Near-End CSU Type
field using the
change ds1
form to
other
.
If this error remains after plugging the CSU Module/ T1 Sync Splitter into
the board’s connector, there could be a problem with the I/O connector
panel.
i. CSU Module/T1 Sync Splitter not expected. The 120A1 CSU Module/T1
Sync Splitter is physically connected to the TN767E board on the back of
the port carrier but the
Near-End CSU Type
field on the
add ds1
form
has not been administered as
integrated
.
If the 120A1 CSU Module/T1 Sync Splitter is to be used, use the
change
ds1
command to change the
Near-End CSU Type
field to
integrated
.
Otherwise, physically remove the 120A1 CSU Module/T1 Sync Splitter
from the back of the port carrier.
j. DS1 configuration error. Attempting to use the 120A1 CSU Module with a
TN767E circuit pack that is configured for 32-channel (2.048 Mbps)
operation. The CSU Module only works with a DS1 board configured for
24-channel (1.544 Mbps) operation in the United States of America.
k. DS1 circuit pack suffix incorrect for CSU Module/T1 Sync Splitter. The
Near-End CSU Type
field on the
add ds1
form has been administered
as
integrated
but the DS1 circuit pack is not a TN767E or later suffix
DS1 board.
If the 120A1 CSU Module/T1 Sync Splitter is to be used, remove the circuit
pack and replace it with a TN767E or later suffix board. Otherwise, use the
change ds1
command to change the
Near-End CSU Type
field to
other
.
l. BLB failure. This error occurs when the DS1 Board Loopback (BLB)
demand test fails. Repeat the test using the following commands:
busyout board UUCSS
,
test ds1-loop UUCSS ds1/csu-loopback-tests
,
release board UUCSS
. If the BLB test continues to fail, then the TN767E
circuit pack needs to be replaced.