Maintenance Objects
3-1145TONE-PT (Tone Generator)
3
Tone Generator Update/Audit Test (#41)
The tone generation facility is refreshed with all the time slot tone information.
This test also triggers in-line error messages the Tone-Clock circuit pack
generates when it detects problems by itself.
A check is also made between the type of tone-clock being tested and the type
of tone-clock needed based on system administration. The administration on the
system-parameters country-options form requires a TN2182 circuit pack.
Tone Generator Crosstalk Test (#90)
This test checks the ability of the Tone Generator to talk on a specific time slot.
The other idle time slots are checked to make sure the Tone Generator put the
tone on only the specified time slot.
Table 3-503. TEST #41 Tone Generator Update/Audit Test
Error
Code
Te st
Result Description/ Recommendation
none ABORT The system was not able to allocate all the resources needed for this test.
2100 ABORT System resources required for this test are not available.
1 FAIL The system requires a TN2182 tone-clock to support the currently
administered country-options tone generation parameters.
1. Check the administration on the system-parameters country-option
form. Specifically, the Base Tone Generation Set on page 1 and any
custom tone administration beginning on page 2.
2. Replace existing tone-clock circuit packs with a TN2182.
2 FAIL The system requires TN2182 tone-clocks to support the currently
administered country-options tone generation parameters.
1. Check the administration on the system-parameters country-option
form. Specifically, the Base Tone Generation Set on page 1 and any
custom tone administration beginning on page 2.
2. Replace existing tone-clock circuit packs with TN2182s.
PASS The tone generation facility has been successfully refreshed with its
time-slot translation and system administration is consistent with this type
of tone-clock.
1. Display the Hardware Error Log via the display errors command to
make sure this circuit pack did not generate new errors.
Continued on next page