DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-293BRI-SET, ASAI-ADJ, BRI-DAT
3
Notes:
a. Errors of this type indicate violations of the ISDN-BRI signaling protocol;
timers associated with certain Layer 3 messages have expired before a
required response was received. InTable 3-128
, the Aux Data field
indicates which timer has just expired. (For more information, refer to the
Lucent ISDN-BRI Specification.)
3073(j) 0 BRI Remote
Loop Back
(#627)
WARNING OFF test station ext l
r 2
test
data-module ext
l r 2
3329(k) Any Signaling Link
Status (626)
WARNING MAJOR/
WARNING
2
OFF †
3584 0, 1 None
3585-
3839(i)
0None
3840-
4095(m)(
n)
0None
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. Major alarms on this MO may be downgraded to Warning alarms based on the value used in the
set options command.
Table 3-127. BRI-SET/ASAI-ADJ Error Log Entries — Continued
Error
Type
Aux
Data
Associated
Test
Alarm
Level
BRI-PORT
Alarm Level
ABRI-PORT
ATT-PORT
LGATE-PORT
ATTE-PT
On/
Off
Board
Test to Clear
Value
Continued on next page