Maintenance Objects
3-658ETR-PT (Enhanced Tone Receiver Port)
3
System Technician-Demanded Tests: Descriptions
and Error Codes
Always investigate tests in the order presented in the following tables when
inspecting errors in the system. By clearing error codes associated with the
Tone
Detection Verification Test
, for example, you may also clear errors generated from
other tests in the testing sequence.
Tone Detection Verification Test (#42)
This test checks out a single ETR port in the touch-tone receiver mode MFC tone
detection/generation mode and general purpose tone detection mode. During
the first portion of the test, the touch-tone receiver mode is tested. Then general
purpose call progress and maintenance tones are tested and lastly MFC tones
are tested.
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
1. D = Destructive; ND = Nondestructive
Tone Detection Verification Test (#42) X X ND
Tone Detection Audit/Update Test (#43) X X ND
Table 3-273. TEST #42 Tone Detection Verification Test
Error
Code
Te s t
Result Description/ Recommendation
none ABORT The system was not able to allocate all the resources needed for this test
OR there was an Internal System Error.
1 ABORT The system could not allocate all the resources needed to test the tones.
1001 ABORT The system was unable to put the ETR-PT in the appropriate mode to test
it.
1002 ABORT The system could not allocate time slots for the test connection. This
situation could occur when the system is heavily loaded. If the system is
not heavily loaded, then test the TDM-BUS via the test tdm command.
Refer to TDM-BUS for details.
1. Retry the command at 1-minute intervals a maximum of 5 times.
Continued on next page