DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-807MEDPROPT (TN802 MED PRO DSP PORT)
3
Notes:
a.
Error Type 1
- this error type indicates that less than three DSPs are out of
service (OOS), and no alarm is raised. The Aux Data field contains the
number of DSPs that are Out of Service (OOS).
b.
Error Type 258
- this error type indicates that more than three, but less
than 9 DSPs are out of service (OOS), and a WARNING alarm is raised.
The Aux Data field contains the number of DSPs that are Out Of Service
(OOS).
c.
Error Type 515
- this error type indicates that all DSPs are out of service
(OOS), and a MINOR alarm is raised. The Aux Data field contains the
number of DSPs that are Out Of Service (OOS).
d.
Error Type 18
- the MEDPRO has been busied out by a
busyout port
UUCSS
command.
1. Release the port (
release port UUCSS
).
515(c) DSP Capacity
Query Test
(##1382)
MINOR ON test board UUCCSS l r5
18(d) 0 busyout port
UUCSS
WARNING OFF release port UUCCSS
769 Any TDM NIC
Looparound Test
(#1380)
MIN ON test port UUCCSS l r10
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.