DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-294BRI-SET, ASAI-ADJ, BRI-DAT
3
The switch sent a message to the endpoint which did not respond in the
allotted time. This can happen occasionally due to failure of the
point-to-point signaling link or because of a problem in the BRI endpoint or
ASAI adjunct or Lucent adjunct. Execute the
test station extension sh
command and pay particular attention to the results of the BRI Layer 3
Query Test (#629). If this test fails, follow the repair procedure for Test
#629.
b. This error type indicates that the circuit pack has been removed or has
been insane for more than 11 minutes. To clear the error, replace or
reinsert the circuit pack.
c. This error occurs when the endpoint does not respond to the service state
query message sent to the adjunct or the endpoint. This error causes an
alarm to be raised. The alarm is retired when the switch receives a
response to the service state query to the endpoint or the adjunct.
For BRI endpoints, the Aux Data field for this error contains "0." When it
occurs, execute the
test station
<extension>
sh
command and pay
particular attention to the results of the BRI Layer 3 Query Test (#629). If
this test fails, follow the repair procedure for Test #629.
When this error occurs for an ASAI or Lucent adjunct, the Aux Data field
indicates the state of the ASAI link or Lucent link and whether an invalid
response or no response was received to the query from the switch, as
shown in Table 3-129
:
Table 3-128. Error Type 2 Cause Values
Aux Data Timer Type
2 First T303 (SETUP timer)
3 Second T303 (SETUP timer)
4 T305 (DISConnect timer)
5 First T308 (RELease timer)
6 Second T308 (RELease timer)
10 T316 (RESTart timer)
12 T309 (Layer 2 Failure timer)
16 TM100 (Management Information Message timer 1)
17 TM200 (Management Information Message timer 2)
102 TASAI (ASAI Routing Timer)