DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-662EXT-DEV ADMIN? N (External Device Alarm)
3
EXT-DEV ADMIN? N (External Device
Alarm)
NOTE:
Use this Maintenance Object when the
External Device Alarm
Admin?
field on the
change system-parameters customer-options
form is
set to
n
.
The Processor in carrier A monitors the EXT-DEV alarm leads. The system only
recognizes pairs connected to the 1M and 1m (ALARM MONITOR) leads. Refer
to the
DEFINITY Communications System Generic 1 and Generic 3i Wiring,
555-204-111, for more details.
Hardware Error Log Entries and Test to Clear
Valu es
MO Name (in
Alarm Log)
Alarm
Level Initial Command to Run
1
1. Where P is an appropriate cabinet number determined via the PORT field from the Alarm
or Error Log.
Full Name of MO
EXT-DEV MAJOR test environment P External Device Alarm
EXT-DEV MINOR test environment P External Device Alarm
Table 3-275. Hardware Error Log Entries and Test to Clear Values
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0 Any Any Any test environment UU r2 or
6
1 or 5 Any External Device
Alarm Test (#120)
MAJOR
MINOR
2
2. One port generates a MAJOR alarm; the other port generates a MINOR alarm.
OFF test environment UU r 2 or
6