DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Commands
2-281status health
2
CP
Proportion of the CPU that is dedicated to call processing. This
occupancy has priority over SM and IDLE occupancy categories, and if
needed, takes processor time from these occupancy categories. This
percentage is rounded to the nearest integer.
Idle
Available proportion of the CPU. This percentage is rounded to the
nearest integer.
Active SPE
A or B indicate the active processor complex. When the active
processor complex is locked on-line with lock switching on DUPINT, the
“lock” option displays; otherwise, “auto” displays.
Duplicated?
Duplication status of the SPE component. “y” = duplication;
“n” = no duplication.
SPE Power
Power source for the processor complex. (commercial) When
commercial power is unavailable, battery backup is in use and is
indicated with “backup”.
Time Source
The current timing source. Display values for this field vary according to
timing sources selected. “external” = For Stratum-3 hardware, “internal”
= an internal source, such as a tone clock.
Primary and secondary timing sources must be administered for the
Stratum-4 option. “primary”= the primary administered source is in use,
“secondary” = the administered secondary source is in use. “local” =
neither the primary or secondary sources are in use.
# Logins
Number of current users.
Cab
Assigned cabinet number (1 to the highest system cabinet number).
Emerg Trans
Settings for emergency transfer switches on the maintenance board for
each cabinet. Available options are: auto-on (“auto+” or “a+”), auto-off
(“auto-” or “a-”), “on”, “off”, and “n.a.”. The system defaults to “auto+” or
“auto-”. In this state, emergency transfer activate automatically if the
cabinet fails (“+”=emergency transfer is activate, “-” = emergency
transfer is inactive). “on” = emergency transfer automatically activates.
“off”=the cabinet cannot activate emergency transfers. Duplicated SPEs
systems = switch settings for both processors of the PPN (cabinet 1)
display. In this case, “auto+” is abbreviated “a+”, “auto-” is abbreviated
“a-”, and “off” is abbreviated “of”. “on” does not change. “n.a.” = the
emergency transfer switch setting is unavailable.
Mj
Number of major alarms associated with the cabinet. Asterisks are used
to fill fields when numbers exceed 99.
Mn
Number of minor alarms associated with the cabinet. Asterisks are used
to fill fields when numbers exceed 99.
Wn
Number of warnings associated with the cabinet. Asterisks are used to
fill fields when numbers exceed 99.