Lucent Technologies 555-233-119 Home Theater Server User Manual


  Open as PDF
of 1872
 
DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-1235UDS1-BD (UDS1 Interface Circuit Pack)
3
1015 ABORT Ports on the UDS1 Interface circuit pack have not been busied out to
out-of-service.
1. Enter the busyout board UUCSS command to put all trunks or ports of
the UDS1 Interface circuit pack into the out-of-service state.
2. Retry the command.
1039 ABORT The UDS1 Interface circuit pack is providing timing for the system. Executing
this test could cause major system disruption.
If the UDS1 Interface circuit pack needs to be tested, set the synchronization
reference to another DS1 Interface circuit pack or to the Tone-Clock circuit
pack via the following command sequence:
1. Issue the disable synchronization-switch command.
2. Next, issue the set synchronization UUCSS command.
3. Lastly, issue the enable synchronization-switch command.
1950 ABORT Another loopback/span test is already executing on the DS1 board or the
board is in a network requested loopback mode (Line loopback or Payload
loopback). The hardware error log will indicate whether a Customer Loopback
Jack Test, Far CSU Loopback Test, or the One-Way Span Test is executing or if
the board is in line loopback or payload loopback mode. Only one
long-duration loopback/span tests can be active at a given time. Thus, if a
loopback/span test is already active, that test must be terminated via the
test
ds1-loop UUCSS end-loopback/span-test
command in order to execute this
test.
1951 ABORT The CSU Repeater Loopback Test could not be executed because the 120A1
CSU Module or the 401A T1 Sync Splitter was not physically installed.
Physically connect the 120A1 CSU Module or the 401A T1 Sync Splitter to the
TN464F board on the back of the port carrier.
Table 3-530. TEST #1211 CSU Repeater Loopback Test — Continued
Error
Code
Te s t
Result Description/ Recommendation
Continued on next page