DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-1131TONE-BD (Tone-Clock Circuit Pack)
3
Notes:
a. Error Type 1
This error indicates the circuit pack totally stopped
functioning or it was physically removed from the system.
NOTE:
The alarm is logged approximately 11 minutes after the circuit pack
is removed/SAKI Sanity Test (#53) fails.
If the circuit pack is not present in the system, insert a circuit pack in the
slot indicated by the error to resolve the error.
If the circuit pack is present in the system, it is faulty and must be
replaced. See the preceding section, ‘‘How to Replace a Tone-Clock
Circuit Pack’’.
b. Error Type 18
The indicated Tone-Clock circuit pack has been made
unavailable via the
busyout tone-clock PC
command. This error applies
only to High or Critical Reliability systems (an active Tone-Clock may not
be busied out). To resolve this error, execute
release tone-clock PC
.
c. Error Type 23
The circuit pack has been logically administered but not
physically installed. Installing the circuit pack will resolve the alarm.
d. Error Type 125
A wrong circuit pack is inserted in the slot where this
circuit pack is logically administered. To resolve this problem, either
remove the wrong circuit pack and insert the logically administered circuit
pack OR use the
change circuit-pack
command to readminister this slot
to match the circuit pack inserted.
e. Error Type 126
The port network specified in the PORT field of the error
log entry booted up without a Tone-Clock circuit pack, or with a one that
cannot communicate at all with the system. The error is logged five
minutes after the port network is restarted. If no circuit pack is present,
install one of the proper code. If there is a circuit pack present, replace it.
3872(p) 0 None set tone-clock PC
override
3999 (q) Any None
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. Minor alarms on this MO may be downgraded to Warning alarms based on the value used in the
set options command.
Table 3-497. Tone-Clock Circuit Pack Error Log Entries — Continued
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
Continued on next page