3-616DS1-BD (DS1 Interface Circuit Pack)
3
Table 3-254. TEST #1215 Inject Single Bit Error Test
Error
Code
Te st
Result Description/ Recommendation
ABORT Internal system error
1. Retry the
test ds1-loop UUCSS inject-single-bit-error
command at
1-minute intervals a maximum of 5 times.
1015 ABORT Ports on the DS1 Interface circuit pack have not been busied out to
out-of-service.
1. Enter the busyout board UUCSS command to put all trunks or ports of the
DS1 Interface circuit pack into the out-of-service state.
2. Retry the command.
ABORT Internal system error
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2000 ABORT Response to the test was not received within the allowable time period. This
may be due to hyperactivity. Error type 1538 in the error log indicates
hyperactivity. The hyperactive circuit pack is out of service and one or more of
the following symptoms may be exhibited.
1. The DS1-BD tests (such as test 138 and test 139) are aborting with error
code 2000.
2. The tests run on the ports of this circuit pack are returning a no board
result.
3. A busyout or a release command has no affect on the test results.
4. A list config command shows that the circuit pack and the ports are
properly installed.
NOTE:
When hyperactivity occurs, the circuit pack is isolated from the system,
and all of the trunks for this circuit pack are placed into the out of
service state. The system will try to restore the circuit pack within 15
minutes. When no faults are detected for 15 minutes, the DS1 interface
circuit pack is restored to normal operation. All of the trunks for the DS1
interface circuit pack are then returned to the in service state.
Hyperactivity is often caused by the associated facility. In such a case,
faults (such as slips, misframes, or blue alarms) would be entered in the
error log. In addition, many hardware errors would be logged against
the associated trunk circuits. If the facility is OK and the error occurs
again after 15 minutes, escalate this problem.
PASS A single bit error has been successfully injected into an active framed 3-in-24
test pattern.
Continued on next page