DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-780MAPD-BD (MAPD Interface Circuit Pack TN802)
3
Notes:
a. Error Type 1: indicates that the circuit pack has totally stopped functioning
or is not fully administered. The alarm is logged about 15 minutes after the
circuit pack has been removed or 11 minutes after the SAKI Test (#53)
fails.
To be fully administered, a MAPD circuit pack must meet all of these
conditions:
Have an entry in the circuit plan (
change circuit pack
)
Be administered (
add ds1 UUCSS
)
Be physically inserted into the correct slot
If the circuit pack has an entry in the circuit plan and either of the other two
conditions are
not
met, a MINOR alarm is logged. To resolve the error,
either:
1. Make sure the circuit pack is properly administered and that a
functioning MAPD circuit pack is inserted in the correct slot, OR
3585 to
3601 (o)
Any Misframe Alarm Inquiry
Test (#145)
MIN/
WRN
3
OFF test board UUCSS r 6
3840 (p) Any None
3841 (q) 4358
3842 (r) 46097
3843 (s) 46081
3999 (t) Any None
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2. If ports are assigned to the circuit pack, then a minor alarm is raised. If no ports are assigned to
the circuit pack, then a warning alarm is raised. The alarm is raised after the circuit pack has been
missing for a period of 15 minutes. Warning alarms are also raised against any ports administered
on the circuit pack.
3. Minor alarms on this MO may be downgraded to warning alarms based on values set in the set
options command.
4. Major alarms on this MO may be downgraded to minor or warning alarms based on values set in
the set options command.
Table 3-326. MAPD (TN802) Error Log entries — Continued
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
Continued on next page