DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-604DS1-BD (DS1 Interface Circuit Pack)
3
pattern, and returns a PASS result to indicate that the pattern was successfully
sent. If the loopback is not established within the 10 seconds, the test returns
FAIL.
The status of the CPE Loopback Jack test will be available in the hardware error
log via error type 3900. Several distinct aux values will be used to give the user
information of the status of the test.
The
list measurements ds1 summary
command will display the length of time the
test has been running (
Test Duration
field) and number of bit errors detected
(
Loopback/Span Test Bit-Error Count
field). If the test pattern is being passed
through the loopback cleanly, the number of bit errors should be very low. The
command will also display the type of loopback/span test executing (
Tes t
field),
the type of pattern generated for the loopback/span test (
Pattern
field), and
whether the pattern (
3-in-24 Pattern
) is synchronized (
Synchronized Field
).
To terminate the test, enter
test ds1-loop UUCSS end-loopback/span-test
command or the
release board
. Using the
release board
command restores all
trunks or ports on the TN767E DS1 Interface circuit pack to the in-service state.
Table 3-251. TEST #1212 CPE Loopback Jack Test
Error
Code
Test
Result Description/ Recommendation
ABORT Internal system error
1. Retry test ds1-loop UUCSS cpe-loopback-jack-test-begin at 1-minute
intervals a maximum of 5 times.
1005 ABORT CPE Loopback Jack Test cannot be executed in the current configuration. To
run this Test, the TN767E or later suffix DS1 must be administered for
24-channel operation. The "Bit Rate" field on the DS1 circuit pack administration
form must be set to "1.544" for 24-channel operation.
1015 ABORT Ports on the DS1 Interface circuit pack have not been busied out to
out-of-service.
1. Enter the busyout board UUCSS command to put all trunks or ports of the
DS1 Interface circuit pack into the out-of-service state.
2. Retry the command.
Continued on next page