DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-905PKT-INT (Packet Interface)
3
Table 3-388. TEST #884 Memory Checksum Test
Error
Code
Test
Result Description/ Recommendation
1006
1137
ABORT Packet Interface is in the out-of-service state so normal maintenance tests
will not run.
1. Use the
display system-parameters maintenance
command to
identify which C-LAN circuit pack is administered with the Bus
Bridge. Verify that the C-LAN circuit pack is present and is not
alarmed.
2. Request a Packet Interface reset using the
reset
packet-interface AS
command. Refer to the Packet Interface
Reset Test (#889) repair procedures for further action.
1334 ABORT The Packet Interface command queue is full. This should be a temporary
condition caused by a high rate of commands being sent to a Packet
Interface. Continued operation with a full command queue will cause a
system WARM restart that may escalate to more severe restart levels.
1. Retry the command at 10-second intervals, a maximum of 5
times.
2000 ABORT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals, a maximum of 3 times.
2500 ABORT Internal system error.
1. Retry the command.
NO
BOARD
The Packet Interface is not detected as being physically present.
1. Reboot the system, then retry the command. If the NO BOARD
indication persists, replace the TN798 Processor circuit pack.
1537 FAIL The Boot PROM memory checksum test failed. The Packet Interface may still
be operational.
1. Retry the command.
2. If the same error code occurs, replace the TN798 Processor
circuit pack at a time that would cause the least disruption of
service. The Packet Interface is still functional but should be
replaced since it may not operate after a system reboot and it will
enter a fatal fault state if it is reset for other reasons.