Lucent Technologies 555-233-119 Home Theater Server User Manual


  Open as PDF
of 1872
 
DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-253ATM-TRK (Circuit Emulation Service Circuit Pack)
3
3 FAIL Distorted tone returned
1. Test the active tone clock on the port network, and verify that a tone is
reaching the ATM-TRK circuit pack. If not, correct the condition.
2. Run test board UUCSS long.
3. If the test continues to fail, replace the ATM-TRK circuit pack.
4. Run test board UUCSS long.
4 FAIL Unable to create TDM-path loop.
1. Retry the command up to 3 times at 1-minute intervals.
2. If this test continues to fail, replace the ATM-TRK circuit pack.
3. Run test board UUCSS long.
5 FAIL Unable to create packet-path loop.
1. Retry the command up to 3 times at 1-minute intervals.
2. If this test continues to fail, replace the ATM-TRK circuit pack.
3. Rerun test board UUCSS long.
6 FAIL A previously established looparound was not released.
1. Run reset board UUCSS.
2. Retry the command up to 3 times at 1-minute intervals.
3. If this test continues to fail, replace the ATM-TRK circuit pack.
4. Rerun test board UUCSS long.
PASS The non-optical parts of the ATM-TRK circuit pack are functioning properly.
0NO
BOARD
ATM-TRK circuit pack not found
1. Check the error log for Error 125 (wrong board) or Error 131 (no board),
and correct as necessary.
2. Check that the board is properly translated and inserted.
3. Check for Error 1538 (hyperactivity), and run reset board UUCSS if
necessary.
4. Rerun test board UUCSS long.
5. If the test fails, replace the board, and rerun test board UUCSS long.
Table 3-111. ATM Board Framer Looparound Test (#1260) — Continued
Error
Code
Tes t
Result Description/ Recommendation
Continued on next page